What Size Dual-Element Fuse for a 28A Motor?
What size dual-element fuse for a 28A motor is a two-step question, and the second step is where most people lose the point. Table 430.52 gives you the percentage. Then you have to check whether the number you calculated is even a size you can buy. Work both steps in order and the answer is 50 amps.
Exam-style question (Sparky QOTD)
A motor has a table full-load current of 28 amps. What is the maximum permitted dual-element, time-delay fuse per 430.52?
A. 70 amps
B. 60 amps
C. 45 amps
D. 50 amps
Answer: D) 50 amps. Table 430.52 puts a dual-element fuse at 175% of FLC: 28 × 1.75 = 49 amps, and Exception 1 rounds that up to the next standard size, 50 amps.
Where to Find It
Open your Code book to Table 430.52 in Article 430. Find the row for a dual-element, time-delay fuse and read the percentage: 175%. Multiply it out: 28 amps × 1.75 = 49 amps. Then turn to 430.52(C)(1) Exception 1. Because 49 amps is not a standard size under 240.6, Exception 1 permits the next standard size up: 50 amps. Tab it: Article 430, "Table 430.52" — dual-element fuse, 175%.
Why This Is the Answer
Start with the device name, because Table 430.52 is organized by device. The stem asks for a dual-element, time-delay fuse, and that row is 175% of full-load current. The math is simple: 28 × 1.75 = 49. If you stop there, you will not find 49 amps anywhere in the options, and that is the signal to keep reading instead of guessing.
The Code expects that problem. Section 430.52(C)(1) Exception 1 covers the case where the Table 430.52 value does not correspond to a standard rating: you may go to the next standard size up. Standard sizes come from 240.6, and the next standard size above 49 amps is 50 amps. So the maximum permitted fuse is 50 amps — not the calculated 49, and not a jump to 60 or 70 amps.
Look at the other options with that rule in mind. The 45-amp option rounds the wrong way, down instead of up. The 60-amp and 70-amp options skip a standard size and overshoot what Exception 1 allows. Only 50 amps follows both steps: the right percentage from the right row, then one standard size up. Drill the same round-up rule on a breaker next in the 22A motor breaker question.
Exam Tip
When your Table 430.52 math lands on a number that is not in the options, do not panic and do not pick the closest value below it. That is Exception 1 doing its job. Check 240.6, take the next standard size up, and move on. The exam puts the non-standard result in the stem on purpose to see if you know the second step exists.