What Size Equipment Grounding Conductor for a 200 Amp Circuit?

What size equipment grounding conductor for a 200 amp circuit comes straight out of Table 250.122. The equipment grounding conductor follows the breaker. Find the overcurrent device rating, read across to copper, and the table gives you the minimum size. For 200 amps, that read is 6 AWG copper. No calculation. No guessing.

Exam-style question (Sparky QOTD)

The equipment grounding conductor for a 200A circuit is sized from Table 250.122 as:

A. 8 AWG copper
B. 6 AWG copper
C. 4 AWG copper
D. 3 AWG copper

Answer: B) 6 AWG copper. Table 250.122 ties a 200A overcurrent device to 6 AWG copper.

Where to Find It

Open your Code book to Table 250.122. The lookup path is simple: find the overcurrent device rating down the left side, then read across to the copper column. For a 200A overcurrent device, that read is 6 AWG copper. Write the tab note the way the bank puts it: Table 250.122, the EGC reads off the breaker size, 200A = 6 AWG.

Why This Is the Answer

The key idea is in that tab note. The equipment grounding conductor reads off the breaker size. You do not size it from the load, and you do not size it by picking a wire that looks close. You size it from the overcurrent device, using Table 250.122, because that is the table the stem names and the table the explanation uses.

Work the read step by step. Left side first: 200A. Then move across to the copper column. The value there is 6 AWG. That is option B. The stem asks what the conductor is sized as from this table, so the row decides the answer. Once your finger is on the 200A row, the question is over. Everything else is just checking that you did not drift a row up or down.

Check the other options against that read. Option A, 8 AWG copper, is smaller than the table requires for a 200A device. Options C and D, 4 AWG and 3 AWG copper, are larger than the table requires here. Bigger is not the answer when the question asks for the table size, and smaller fails the minimum. Only 6 AWG matches the 200A row in the copper column. If you want another rep in the same table, work the 100-amp equipment grounding conductor question next.

Exam Tip

When you see equipment grounding conductor in a stem, go straight to Table 250.122 and start with the breaker size. Say the pairing out loud as you read it: breaker first, copper column second. The table read takes ten seconds. Memory is how the smaller wrong answer gets picked, and oversizing from habit is how the bigger wrong answers get picked.