What Size Equipment Grounding Conductor for a 40 Amp Circuit?

What size equipment grounding conductor for a 40 amp circuit is a one-row table read in Table 250.122. The stem names the table and asks for the minimum copper size, so there is nothing to calculate. Find the 40-amp row, read across to copper, and you get 10 AWG. The trap is reaching for a smaller wire because the circuit itself feels small.

Exam-style question (Sparky QOTD)

A 40-amp circuit requires what minimum copper equipment grounding conductor per Table 250.122?

A. 14 AWG
B. 12 AWG
C. 10 AWG
D. 8 AWG

Answer: C) 10 AWG. Table 250.122 gives 10 AWG copper for the 40-amp row.

Where to Find It

Open your Code book to Table 250.122 in Article 250. Find the 40-amp rating, then read across to the copper column. The value there is 10 AWG copper. Write the tab note the way the bank puts it: Article 250, "Table 250.122," and next to it, "40 and 60 share the 10 AWG row." That shared row is the detail this question is really testing.

Why This Is the Answer

The bank explanation states it plainly: in Table 250.122, both the 40-amp and 60-amp rows are 10 AWG copper. Two different overcurrent ratings, one equipment grounding conductor size. That is why this stem shows up on practice tests. It catches people who assume every step up in breaker size means a step up in grounding conductor size. The table does not work that way here, and the read proves it in about ten seconds.

Work it the same way every time. Start at the rating the stem gives you: 40 amps. Stay on that row. Move across to copper. You land on 10 AWG, which is option C. Because the question asks for the minimum, you stop at the table value instead of jumping to a larger wire out of caution. The table already set the minimum, and the stem told you to use the table.

Check the other options against that read. Options A and B, 14 AWG and 12 AWG, are both smaller than the 40-amp row allows, so either one fails the minimum the question asks for. Option D, 8 AWG, is larger than the table requires for this row. Only 10 AWG matches the row, and it matches the 60-amp row too, which makes it easy to lock in once you have seen it. If you want a bigger-circuit rep in the same table, work the 150-amp equipment grounding conductor question next.

Exam Tip

Do not size the equipment grounding conductor from the feel of the circuit. A 40-amp circuit feels like small work, and that feeling is exactly what pulls people toward 12 or 14 AWG. Trust the row instead. And use the shared-row note as a memory hook: if you remember that 60 amps takes 10 AWG copper in this table, you already know 40 amps too.

Keep Drilling