Practice question · NEC Table 250.122
What Size Equipment Grounding Conductor for a 400 Amp Feeder?
What size equipment grounding conductor for a 400 amp feeder is a straight table read, if you go to the right table first. Table 250.122 sizes the equipment grounding conductor from the overcurrent device ahead of it. Find 400 amps, read across to copper, and you are done. The trap is grabbing a nearby row or a nearby answer that belongs to a smaller breaker.
Exam-style question (Sparky QOTD)
The equipment grounding conductor for a 400A feeder is sized from Table 250.122 as:
A. 6 AWG copper
B. 4 AWG copper
C. 2 AWG copper
D. 3 AWG copper
Answer: D) 3 AWG copper. Table 250.122 ties a 400A overcurrent device to a 3 AWG copper equipment grounding conductor.
Where to Find It
Open your Code book to Table 250.122. This table lives in Article 250 and sizes equipment grounding conductors by the rating of the overcurrent device in the circuit. Find the 400A overcurrent device, then read across to the copper column. That read gives you 3 AWG copper. Tab it exactly like that: Table 250.122, and do not confuse it with the 4 AWG used at 300A.
Why This Is the Answer
Start with what the stem gives you. It names the table, Table 250.122, and it gives you the number that drives the read: 400A. That 400A is the overcurrent device rating, not a load you calculate and not a conductor ampacity you look up somewhere else. Your only job is to match that rating in the left side of the table and read across.
Run the options against that read. Option D, 3 AWG copper, is the table answer for a 400A overcurrent device. Option B, 4 AWG copper, is the close trap. The bank explanation calls it out directly: do not confuse the 400A answer with the 4 AWG used at 300A. One row off is one size off, and on the exam one row off is simply wrong.
The other options fail the same test. Option A, 6 AWG copper, is smaller than the table requires for 400A. Option C, 2 AWG copper, is bigger than the table requires, and the question asks what Table 250.122 sizes it as, not what would also work in the field. Stick to the exact row, the exact column, and the exact answer: 3 AWG copper. For a companion read in the same table, see the 150-amp equipment grounding conductor question.
Exam Tip
On test day, say the lookup out loud before you touch the options: Table 250.122, 400A overcurrent device, copper column. That order stops you from drifting to the 300A row and its 4 AWG answer. Tab Table 250.122 in your book so you can land on it in seconds.