Practice question · NEC Table 250.66
What Size Grounding Electrode Conductor for 250 kcmil Copper?
What size grounding electrode conductor for 250 kcmil copper comes straight out of Table 250.66. The grounding electrode conductor reads off the service-entrance conductors, not off a breaker. Find the service conductor size in the table, read across to copper, and the table gives you the minimum size. For 250 kcmil copper, that read is 2 AWG copper.
Exam-style question (Sparky QOTD)
The grounding electrode conductor for 250 kcmil copper service-entrance conductors is sized from Table 250.66 as:
A. 6 AWG copper
B. 4 AWG copper
C. 2 AWG copper
D. 1/0 AWG copper
Answer: Answer: C) 2 AWG copper. Table 250.66 ties 250 kcmil copper service-entrance conductors to a 2 AWG copper grounding electrode conductor.
Where to Find It
Open your Code book to Table 250.66. The lookup path is simple: find the size of the largest service-entrance conductor down the left side, then read across to the copper grounding electrode conductor column. For 250 kcmil copper service-entrance conductors, that read is 2 AWG copper. Write the tab note the way the bank puts it: Table 250.66, the GEC reads off the service conductor size, and 250 kcmil lands on 2 AWG.
Why This Is the Answer
The key idea is in that tab note. The grounding electrode conductor reads off the service conductor size. You do not size it from the load, and you do not size it from an overcurrent device. Table 250.66 pairs service-entrance conductors with a grounding electrode conductor, and the stem hands you the input the table wants: 250 kcmil copper service-entrance conductors. Once you have the right input, the question is a one-row read.
Work the read step by step. Left side first: 250 kcmil copper. Then move across to the copper column for the grounding electrode conductor. The value there is 2 AWG. That is option C. The stem even names the table for you, so there is no table hunt here. Your only job is to land on the correct row and read the correct column without drifting to a neighboring size.
Check the other options against that read. The 6 AWG and 4 AWG options are smaller than what the table requires for 250 kcmil service conductors, and the 1/0 AWG option is larger than the table calls for here. Bigger is not the answer when the question asks for the table size, and smaller fails the minimum. Only 2 AWG matches the 250 kcmil row. If you want the larger-service version of this same read, work the 500 kcmil grounding electrode conductor question next.
Exam Tip
When you see grounding electrode conductor in a stem, ask one question before you open the book: what size are the service-entrance conductors? That size is your row in Table 250.66. Say the pairing out loud as you read it: service conductors first, GEC column second. The read takes ten seconds, and it keeps the breaker-based tables out of a service-based question.