Which table sizes the main bonding jumper is a matching question, and Article 250 is full of them. Four tables sit close together and do four different jobs. For the main bonding jumper, the answer is Table 250.102(C)(1). Per 250.28(D)(1), that table sizes the jumper based on the area of the largest ungrounded conductor.

Exam-style question (Sparky QOTD)

Per 250.28(D)(1), the main bonding jumper is sized per:

A. Table 250.102(C)(1)
B. Table 310.16
C. Table 250.66
D. Table 250.122

Answer: A) Table 250.102(C)(1). The main bonding jumper follows Table 250.102(C)(1).

Where to Find It

Open your Code book to Article 250. Start at 250.28(D)(1), which sends you to Table 250.102(C)(1) for the main bonding jumper. That table sizes the jumper based on the area of the largest ungrounded conductor. Tab this location and write the bank note on it: bonding jumpers live in 250.102. When a stem says bonding jumper, your hand should move there first.

Why This Is the Answer

The stem gives you the rule section and asks which table does the sizing. Section 250.28(D)(1) points to Table 250.102(C)(1), and that table is based on the area of the largest ungrounded conductor. That basis matters. It tells you the main bonding jumper is tied to the size of the ungrounded conductors, which is a different starting point from the tables in the other options.

Each wrong option is a real table with a different job. Table 250.66 sizes grounding electrode conductors. Table 250.122 sizes equipment grounding conductors off the overcurrent device. Table 310.16 is a conductor ampacity table, not a bonding jumper table at all. The exam builds these questions by putting neighboring tables in one option list. If you match the noun in the stem, bonding jumper, to the section that covers bonding jumpers, you cut through the list fast.

Use the noun-matching habit across Article 250. Grounding electrode conductor, equipment grounding conductor, and bonding jumper sound similar, and the Code gives each one its own sizing path. Underline the exact noun in the stem, then go to the table that carries that noun. For a water pipe version of the same habit, see the metal water pipe bonding jumper question.

Exam Tip

In Article 250, match the noun before you match a number. Bonding jumper means 250.102. If you jump to the first grounding table you find, you will land on 250.66 or 250.122 and pick a confident wrong answer. Slow down for the noun, and the table picks itself.

Keep Drilling