What Is the Maximum Breaker Size for a 28A Motor?

The maximum breaker size for a 28A motor is a percentage problem, not a memory problem. The motor in this question has a full-load current of 28A. Table 430.52 gives you the percentage for an inverse-time circuit breaker, and one multiplication gives you the rating. Work it in that order and the answer is 70A.

Exam-style question (Sparky QOTD)

For that same motor (28A FLC), what is the maximum rating of an inverse-time circuit breaker protecting the branch circuit?

A. 50A
B. 70A
C. 84A
D. 35A

Answer: Answer: B) 70A. Table 430.52 sets an inverse-time breaker at 250% of FLC, and 28 × 2.5 = 70A.

Where to Find It

Open your Code book to Article 430, Table 430.52. Find the row for an inverse-time circuit breaker and read the percentage: 250% of FLC. Tab this table. The bank's tab note puts the three numbers you will use most side by side: 250% for an inverse-time breaker, 300% for a non-time-delay fuse, and 175% for a time-delay fuse. This stem asks for the breaker, so 250% is the only percentage that matters here.

Why This Is the Answer

Start with the two facts the stem hands you. The full-load current is 28A, and the device is an inverse-time circuit breaker. Table 430.52 ties that device to 250% of FLC. Now do the one step of math the question actually tests: 28 × 2.5 = 70. The maximum rating is 70A, and that is option B. There is no second table and no second step hiding behind this one.

The word maximum matters. The table percentage is a ceiling for the branch-circuit short-circuit and ground-fault device, and the question asks for that ceiling directly. You are not picking the breaker you would reach for first. You are reporting the largest rating Table 430.52 allows for this motor and this device type, and the table answers that with a percentage, not a wire size or a load calculation.

Check the other options against the table before you move on. The 84A option is the trap with real math behind it: 28 × 3 = 84, and 300% is a real percentage in this same table, but it belongs to a non-time-delay fuse, not to an inverse-time breaker. The 50A and 35A options match no percentage the table gives for this device. Only 70A is 250% of 28A. If you want the fuse side of this same table, work the 22A motor fuse question next.

Exam Tip

Read the device type before you read the percentage. Breaker, non-time-delay fuse, and time-delay fuse each carry a different number in Table 430.52, and the options are built from those other rows on purpose. Underline inverse-time in the stem, say 250% out loud, then multiply. Five seconds of naming the device keeps the fuse math out of a breaker question.