Practice question · NEC 430.52(C)(1)
What If a Motor Breaker Trips on Starting Current?
What if a motor breaker trips on starting current, even though you sized it right off the table? Article 430 has a specific answer for that exact failure. Section 430.52(C)(1) Exception 2 lets you increase the breaker, but only up to a hard ceiling: 400 percent of full-load current. Know the ceiling and this question takes ten seconds.
Exam-style question (Sparky QOTD)
An inverse-time breaker sized at 250 percent of motor FLC trips on starting current. Per 430.52(C)(1) Exception 2, what is permitted?
A. The next higher standard breaker rating
B. 400 percent of full-load current
C. A fused switch only
D. Removing the breaker
Answer: B) 400 percent of full-load current. Exception 2 permits increasing the breaker when the Table 430.52 rating is not sufficient for starting current, up to 400% of FLC.
Where to Find It
Open your Code book to 430.52(C)(1) in Article 430 and read both exceptions. Exception No. 2 covers this stem: where the rating from Table 430.52 is not sufficient for the starting current of the motor, it may be increased, but not to exceed 400 percent of full-load current for motors with a full-load current of 100 amperes or less, or 300 percent for motors over 100 amperes. Tab it: Article 430, 430.52(C)(1) — read both exceptions; they solve different problems.
Why This Is the Answer
The stem names the exception, so your job is to match the problem to the right one. The problem here is starting current: the breaker was sized at 250 percent of FLC and it trips when the motor tries to start. Exception No. 2 is written for exactly that situation, and its permission comes with a cap. For a motor at 100 amperes or less, the cap is 400 percent of full-load current, which is the answer the stem is asking for.
Option A is the trap, and it is a good one. The next higher standard breaker rating is real Code language, but it belongs to Exception No. 1, which solves a different problem: the Table 430.52 value does not correspond to a standard rating. Nothing in this stem says the size is non-standard. The stem says the breaker trips on starting current, and that phrase points to Exception 2 every time.
Options C and D are not permissions in 430.52(C)(1) at all. The Code does not tell you to swap in a fused switch only, and it never tells you to remove the breaker. When two options invent a fix the section never mentions, cross them out and choose between the two real exceptions. We work the companion case in the motor breaker that won't start question.
Exam Tip
Learn the two 430.52(C)(1) exceptions as a pair. Exception 1: the number is not a standard size, so go one size up. Exception 2: the breaker will not hold through starting, so you may increase it, capped at 400 percent for motors of 100 amps or less and 300 percent above that. Read the stem for which problem it describes, then pick that exception's answer.
Keep Drilling