Practice question · NEC Table 250.122
What Size EGC Does a 400 Amp Feeder Need?
What size EGC a 400 amp feeder needs comes straight out of Table 250.122. The equipment grounding conductor follows the overcurrent device ahead of it. Find the 400-amp row, read across to copper, and the table gives you the minimum size. For 400 amps, that read is 3 AWG copper. The whole question turns on reading the right row.
Exam-style question (Sparky QOTD)
A 400-amp feeder requires what minimum copper EGC per Table 250.122?
A. 3 AWG
B. 2 AWG
C. 6 AWG
D. 4 AWG
Answer: Answer: A) 3 AWG. Table 250.122 ties a 400A overcurrent device to 3 AWG copper.
Where to Find It
Open your Code book to Table 250.122. Find the overcurrent device rating down the left side, then read across to the copper column. For a 400A overcurrent device, that read is 3 AWG copper. Write the tab note the way the bank puts it: read the OCPD row, not the conductor row. That one line is the difference between the right answer and the trap on this question.
Why This Is the Answer
The bank's tab-to-it note names the trap directly: read the OCPD row, not the conductor row. Table 250.122 is organized by the rating of the overcurrent device protecting the circuit. The feeder conductors themselves are not the input. So the first move is to find 400 in the overcurrent column, because 400 amps in this stem is the device rating the table wants you to start from.
Work the read step by step from there. Left side first: the 400A overcurrent row. Then move across to the copper column. The value there is 3 AWG. That is option A. The stem asks for the minimum copper EGC per this table, so the row decides the answer. Once your finger is on the 400A row, the question is over. Everything else is just checking that you did not drift a row up or down while reading across.
Check the other options against that read. The 6 AWG option is well under what the table requires for a 400A device, and the 2 AWG and 4 AWG options do not match the 400A row in the copper column. Only 3 AWG is the value Table 250.122 prints for this rating. If you want another rep in the same table at a smaller rating, work the 200-amp equipment grounding conductor question next.
Exam Tip
When you see EGC or equipment grounding conductor in a stem, go straight to Table 250.122 and start with the breaker or fuse rating. Say the pairing out loud as you read it: OCPD first, copper column second. Do not start from the feeder conductor size. That is the row mix-up this question is built to catch, and naming the input before you read fixes it.
Keep Drilling
This is one of 33 NEC topics. Sparky's 1,087 codebook-first questions drill all of them — every question a lookup rep with your book open, 15 minutes a day.