Practice question · NEC Table 250.122

What Size Equipment Grounding Conductor for a 300 Amp Circuit?

The equipment grounding conductor for a 300 amp circuit is sized off the overcurrent device, not off the circuit conductors. Table 250.122 makes that link direct: a 300-amp overcurrent device calls for 4 AWG copper. Find the breaker rating down the left column, read across, and you are done. The EGC follows the breaker.

Exam-style question (Sparky QOTD)

A 300-amp circuit requires what minimum copper equipment grounding conductor per Table 250.122?

A. 6 AWG
B. 4 AWG
C. 3 AWG
D. 2 AWG

Answer: B) 4 AWG. Table 250.122 lists a 300-amp overcurrent device at 4 AWG copper.

Where to Find It

Open your Code book to Article 250, Table 250.122. Find the breaker rating down the left column. At the 300-amp row, read across to the copper column: 4 AWG. Tab this table in Article 250 and add the bank note: the EGC follows the breaker. That sentence is the lookup. You start from the overcurrent device rating every time.

Why This Is the Answer

This question is a one-table lookup, and the stem tells you which table and which starting point to use. The circuit is protected by a 300-amp overcurrent device. Table 250.122 keys the equipment grounding conductor size to that rating. At 300 amps, the minimum copper equipment grounding conductor is 4 AWG. Option B is that value, read straight from the correct row.

The nearby options are there to catch a sloppy row read. A 6 AWG answer is too small for this row, and 3 AWG and 2 AWG belong to larger overcurrent ratings further down the table. If you land one row high or one row low, you still get a real size from the same table, just not the one for 300 amps. That is why you read the left column first and confirm the rating before your eyes move across the page.

Keep this table separate from the other grounding tables in your head. Table 250.122 is the equipment grounding conductor table, and its driver is the overcurrent device. Other grounding questions start from service conductors or from a different component. Matching the table to the component in the stem is half the work. For the next size up, work the 400 amp feeder EGC question and compare the two rows side by side.

Exam Tip

Start every Table 250.122 question by saying the breaker rating out loud. Then find that exact rating in the left column before you read across. Do not start from the wire size, the load, or the conductor material in the middle of the table. The EGC follows the breaker, in that order, every time.