Practice question · NEC Table 250.66
What Size Grounding Electrode Conductor for 1/0 Copper?
What size grounding electrode conductor for 1/0 copper service conductors is a pure table lookup, and Table 250.66 is built around one idea: the grounding electrode conductor follows the service-entrance conductors, not the breaker. Read the conductor row for 1/0 AWG copper and the answer is 6 AWG copper.
Exam-style question (Sparky QOTD)
Service-entrance ungrounded conductors are 1/0 AWG copper. What is the minimum copper grounding electrode conductor per Table 250.66?
A. 8 AWG
B. 6 AWG
C. 4 AWG
D. 2 AWG
Answer: B) 6 AWG. Table 250.66 pairs 1 AWG and 1/0 AWG copper service conductors with a 6 AWG copper grounding electrode conductor.
Where to Find It
Open your Code book to Table 250.66 in Article 250. The left side of the table is the size of the largest service-entrance conductor. Find the row for 1 AWG and 1/0 AWG copper and read across to the copper grounding electrode conductor column: 6 AWG. Tab it: Article 250, "Table 250.66" — read the conductor row, not the breaker row. That is the trap, and the tab note is worth writing word for word.
Why This Is the Answer
Table 250.66 never asks what size the main breaker is. It asks what size the service-entrance ungrounded conductors are. This stem hands you that size directly: 1/0 AWG copper. The 1 AWG and 1/0 AWG row calls for a 6 AWG copper grounding electrode conductor, so 6 AWG is the minimum and the answer.
The wrong options are the neighboring rows, and that is deliberate. The 8 AWG option is one step too small for this row. The 4 AWG and 2 AWG options belong to larger service conductors further down the table. If you drift a row in either direction, you land on a real table value that is wrong for 1/0. Slow down on the row label before you read across.
The bigger habit here is keeping your grounding tables separate. A grounding electrode conductor is sized from the service conductors in Table 250.66. An equipment grounding conductor is a different job with a different driver. Mixing those two lookups is one of the most common ways to miss an easy grounding point. Compare this row with the next size up in the 3/0 copper GEC question.
Exam Tip
When a stem says "grounding electrode conductor" and gives you a service conductor size, go straight to Table 250.66 and put your finger on the conductor row first. Say the row out loud — 1/0 copper — then read across. Never start from the breaker size on a GEC question. The table does not use it, and the exam knows that is where you will reach first.
Keep Drilling