What Size Grounding Electrode Conductor for 3/0 Copper?
What size grounding electrode conductor for 3/0 copper service conductors comes straight out of Table 250.66, and the stem tells you exactly which row to use. The table reads off the service conductor size. For 3/0 AWG copper, the grounding electrode conductor is 4 AWG copper.
Exam-style question (Sparky QOTD)
The grounding electrode conductor for 3/0 AWG copper service-entrance conductors is sized from Table 250.66 as:
A. 8 AWG copper
B. 6 AWG copper
C. 4 AWG copper
D. 2 AWG copper
Answer: C) 4 AWG copper. Table 250.66 pairs 3/0 copper service conductors with a 4 AWG copper grounding electrode conductor.
Where to Find It
Open your Code book to Table 250.66 in Article 250. Find 3/0 AWG copper on the service-entrance conductor side of the table and read across to the copper grounding electrode conductor column: 4 AWG copper. Use the tab trick from the question bank: the GEC table reads off the service conductor size. Do not use the breaker size here. That one note protects you on every question in this family.
Why This Is the Answer
The stem does the setup work for you. It names the table, Table 250.66, and it gives you the input the table needs: 3/0 AWG copper service-entrance conductors. In that row, the copper grounding electrode conductor is 4 AWG. There is no calculation and no demand factor. It is a read-across lookup, and the only way to miss it is to read the wrong row or start from the wrong input.
Check the distractors against the table and you will see the pattern. The 6 AWG option belongs to the smaller 1 AWG and 1/0 AWG row. The 2 AWG option belongs to a larger service further down the table. The 8 AWG option is smaller still. Every option is a real Table 250.66 value, just for a different service size. The exam is not testing whether you know a size. It is testing whether you can land on the 3/0 row and stay there.
Build the row sequence as you drill and these get faster. Smaller services take smaller grounding electrode conductors, and each step up in service size steps the GEC up with it. Work the row below this one in the 1/0 copper GEC question, then the larger services, until reading across Table 250.66 feels automatic.
Exam Tip
Underline the service conductor size in the stem before you open the table. Here that is 3/0 AWG copper. Then find those exact words in the left column of Table 250.66 and read straight across without letting your eyes wander to the breaker rating, which the stem does not even give you. If a GEC stem withholds the breaker size, that is your confirmation: the breaker was never part of this lookup.