What Is the Maximum Inverse-Time Breaker for a Motor?

The maximum inverse-time breaker for a motor is not a guess and it is not the same number as the fuses in the same table. Table 430.52 gives each protective device its own percentage of full-load current. For an inverse-time circuit breaker, that percentage is 250% of FLC. Learn to read the device name first, then the percentage, and this whole family of motor questions gets fast.

Exam-style question (Sparky QOTD)

Per Table 430.52, the maximum rating of an inverse-time circuit breaker protecting a motor branch circuit is:

A. 250% of FLC
B. 300% of FLC
C. 800% of FLC
D. 175% of FLC

Answer: A) 250% of FLC. Table 430.52 sets an inverse-time breaker at 250% of the motor full-load current.

Where to Find It

Open your Code book to Table 430.52. Find the row for an inverse-time circuit breaker and read across to the percentage: 250%. Tab this table. The tab note from the question bank is short and worth copying: breaker 250, fuses 300/175. That one line keeps the breaker row separate from the fuse rows when you are working under time pressure.

Why This Is the Answer

Table 430.52 is organized by device type, and that is the whole point of this question. The stem does not ask for a fuse. It asks for an inverse-time circuit breaker protecting a motor branch circuit. In that row, the maximum rating is 250% of FLC. No other row in the table changes that answer, even though the other percentages in the options are real numbers from the same table.

Look at why each wrong answer tempts you. The 300% option belongs to a nontime-delay fuse. The 175% option belongs to a dual-element, time-delay fuse. The 800% option belongs to an instantaneous-trip breaker. All three are in Table 430.52, and all three are wrong here because the device in the stem is different. The exam is testing whether you match the device to its row, not whether you can memorize one big percentage.

That matching habit pays off across Article 430. Motors show up again and again on the journeyman exam, and the stems change the device, the fuse type, or the wording from maximum to another limit. If you slow down for the device name, you land on the right row every time. If you rush to a familiar number, you pick a fuse answer for a breaker question. Work a related rep next in the 28A motor breaker question, where the same 250% gets multiplied out.

Exam Tip

Underline the device type in the stem before you open the table. Say it plainly: inverse-time breaker, 250%. Then check that the option you pick matches that row and no other. On test day, most Table 430.52 misses are not math errors. They are row errors, and a five-second underline fixes them.

Keep Drilling

This is one of 33 NEC topics. Sparky's 1,087 codebook-first questions drill all of them — every question a lookup rep with your book open, 15 minutes a day.