Dwelling Load Calculation, Step by Step (NEC Article 220)
The dwelling load calculation is the longest question on the journeyman exam, and the most predictable. It is always the same five blocks in the same order: general load, fixed appliances, dryer, range, and heat versus AC. Open your Code book to Article 220 and work it block by block. Rush it and you will grab a nameplate number that the Code tells you to ignore. That is exactly what the wrong answers are built on.
One warning before the math: this topic has two right answers, one per NEC edition. The worked example below uses the 2023 NEC and Article 220, which is what most states still test. If your state tests the 2026 NEC, load calculations moved to Article 120 and two inputs changed. That re-run is in its own section below. Do not mix them. Not sure which edition your state uses? Check the state-by-state edition table first.
Step 1 — The General Load Block
Start with the floor area. Use the outside dimensions of the house [220.12]. A dwelling gets 3 VA per square foot for general lighting and receptacles [220.41, Table 220.12]. A 2,000 sq ft house starts at 6,000 VA.
Two things hide inside that number. First, dwelling receptacles are already included in the 3 VA per square foot [220.14(J)]. Do not add 180 VA per receptacle. That figure is for nondwelling occupancies [220.14(I)], and it is the single most common way this question goes wrong. Second, add the circuits the Code prices separately:
- Small-appliance branch circuits: 1,500 VA each, two minimum [220.52(A)] = 3,000 VA.
- Laundry branch circuit: 1,500 VA [220.52(B)].
That gives you a connected general block of 6,000 + 3,000 + 1,500 = 10,500 VA. You do not carry all of it. Table 220.42 applies the dwelling demand factors: the first 3,000 VA at 100%, the remainder at 35%. So 3,000 + (7,500 × 0.35) = 5,625 VA. That is your general block demand. Write it down and move on.
Step 2 — Dryer, Range, and Fixed Appliances
Each of these has its own rule, and each rule overrides the nameplate in a way the exam loves to test.
- Dryer [220.54]: 5,000 VA or the nameplate rating, whichever is larger. A dryer with a 4.2 kW nameplate still goes in at 5,000 VA. The floor controls, not the plate. One dryer gets no demand reduction.
- Range [Table 220.55]: a single 12 kW range goes in at 8 kW, straight from Column C. Not 12 kW. Over 12 kW, add 5% for each kW over: a 15 kW range is 8 kW × 1.15 = 9.2 kW.
- Fastened-in-place appliances [220.53]: four or more of them (not the range, dryer, AC, or space heat) take a 75% demand factor. Four appliances at 1,100 + 700 + 900 + 600 = 3,300 VA become 2,475 VA. Three appliances get no reduction at all. The count is the rule.
Step 3 — Heat vs. AC: Take the Larger Only
Heating and air conditioning are noncoincident loads [220.60]. The house does not run both at full load at the same time, so you count only the larger one. A house with 12 kW of electric heat and a 7.5 kVA AC unit contributes 12,000 VA, not 19,500 VA. Adding both together is a planted wrong answer on nearly every version of this question.
Lookup tip: tab Article 220 in this order before test day: Table 220.12 for the 3 VA figure, 220.52 for the 1,500 VA circuits, Table 220.42 for the 35% demand, 220.53, 220.54, and Table 220.55. Six tabs, and every dwelling load question on the exam is answered within a few pages of one of them. If your state tests the 2026 NEC, tab Article 120 the same way.
Step 4 — Full Worked Example (2023 NEC)
The question: A 2,000 sq ft one-family dwelling has two small-appliance circuits, one laundry circuit, a 12 kW range, a dryer with a 4.2 kW nameplate, four fastened-in-place appliances (dishwasher 1,100 VA, disposal 700 VA, compactor 900 VA, attic fan 600 VA), 12 kW of electric heat, and a 7.5 kVA AC unit. What service size is required?
Run the blocks:
- General block: 10,500 VA connected → demand 5,625 VA
- Fixed appliances: 3,300 × 0.75 = 2,475 VA
- Dryer: 5,000 VA (the 5,000 VA floor beats the 4,200 VA nameplate)
- Range: 8,000 VA (Table 220.55, Column C)
- Heat vs. AC: 12,000 VA (heat is larger; AC drops out)
Total: 33,100 VA. Divide by 240 V: 33,100 ÷ 240 = 137.9 A. The service has to carry at least the calculated load [230.42], so you round up to the next standard size: a 150 A service. For reference, a one-family dwelling service is never smaller than 100 A [230.79(C)], but here the calculation, not the minimum, sets the size.
If Your State Tests the 2026 NEC
In the 2026 NEC, load calculations moved from Article 220 to Article 120, and the dwelling general lighting load for feeder and service calculations dropped from 3 VA to 2 VA per square foot. Branch circuits still use 3 VA per square foot. Everything else in this house stays the same, so only the general block changes:
- General block connected: (2,000 × 2 VA) + 3,000 + 1,500 = 8,500 VA → demand 3,000 + (5,500 × 0.35) = 4,925 VA
- Everything else identical: 2,475 + 5,000 + 8,000 + 12,000 VA
Total: 32,400 VA ÷ 240 V = 135.0 A → still a 150 A service. That is the teaching point: the edition changes the math, not this house's answer. But on the exam, the intermediate numbers are answer choices too, and a 2026 test graded against 2023 inputs will mark your 5,625 VA general block wrong. Know which book you are being tested on. The 2026 NEC changes quiz runs the other big moves side by side.
The Optional Method, in 30 Seconds
For one-family dwellings, the optional method in Part IV of Article 220 is often faster. Under 220.82(B), you take the first 10 kVA of the general load at 100% and the remainder at 40%. A 28,000 VA general load becomes 10,000 + (18,000 × 0.40) = 17,200 VA. Heat and AC still go in at 100% of nameplate, larger only [220.82(C)].
Testing the 2026 NEC? Same method, one different tier: 120.82(B) puts the first 8 kVA at 100%. That same 28,000 VA load becomes 8,000 + (20,000 × 0.40) = 16,000 VA. If a question says "optional method," check your tier before you multiply anything.
The Traps the Exam Sets for You
- 180 VA per receptacle in a house. Commercial rule. In a dwelling, receptacles ride inside the per-square-foot load.
- The dryer at its 4.2 kW nameplate. The 5,000 VA floor in 220.54 controls.
- The 12 kW range at 12 kW. Column C of Table 220.55 says 8 kW.
- Heat and AC added together. Noncoincident. Larger only.
- The 75% appliance factor with only three appliances. It takes four or more to trigger 220.53.
- The wrong edition's inputs. 3 VA and a 10 kVA tier belong to Article 220. 2 VA and an 8 kVA tier belong to Article 120. Printing one edition's numbers on the other edition's test is a miss either way.
That is the whole method: five blocks, in order, each with its own rule. It pairs with the same discipline as voltage drop: write every block down, apply the demand factor where the Code gives you one, and never trust a nameplate the Code tells you to override.